多聯(lián)機(jī)空氣源熱泵相變蓄能除霜系統(tǒng)實(shí)驗(yàn)研究

發(fā)布時(shí)間:2018-07-06 11:59

  本文選題:多聯(lián)機(jī) + 空氣源熱泵。 參考:《哈爾濱工業(yè)大學(xué)》2014年碩士論文


【摘要】:多聯(lián)機(jī)是未來空氣源熱泵的主要發(fā)展方向之一,但除霜問題嚴(yán)重制約了多聯(lián)機(jī)的進(jìn)一步發(fā)展。為了解決這一難題,在認(rèn)真了解多聯(lián)機(jī)空氣源熱泵工作原理的前提下,設(shè)計(jì)了多聯(lián)機(jī)空氣源熱泵相變蓄能除霜系統(tǒng),分別提出了針對(duì)多聯(lián)機(jī)新系統(tǒng)的正常供熱、相變蓄熱以及蓄能除霜流程。 根據(jù)相變溫度和相變潛熱等多方面考慮,選擇65mol%癸酸+35mol%十二酸為相變材料。提出了根據(jù)多聯(lián)機(jī)空氣源熱泵單次除霜化霜水質(zhì)量計(jì)算除霜能耗的新方法,保證相變材料用量的精確節(jié)省。自主設(shè)計(jì)了翅片型相變蓄熱器并對(duì)其換熱能力進(jìn)行初步的計(jì)算,保證其蓄熱、取熱操作的順利進(jìn)行。 依據(jù)設(shè)計(jì)的實(shí)驗(yàn)流程以及實(shí)驗(yàn)的驗(yàn)證需求,搭建了多聯(lián)機(jī)相變蓄能除霜實(shí)驗(yàn)臺(tái),選擇了測(cè)量工具和數(shù)據(jù)采集系統(tǒng)。進(jìn)行了誤差分析,證明實(shí)驗(yàn)臺(tái)測(cè)量精度滿足使用要求。 在此基礎(chǔ)上,完成了多聯(lián)機(jī)空氣源熱泵的正常供熱/除霜、相變蓄熱/除霜實(shí)驗(yàn),測(cè)量了包括溫度、壓力、相對(duì)濕度、功率等參數(shù)在內(nèi)的供熱、蓄熱、除霜實(shí)驗(yàn)動(dòng)態(tài)數(shù)據(jù);基于以上數(shù)據(jù),研究了多聯(lián)機(jī)常規(guī)供熱、除霜特性,分析了常規(guī)除霜存在的不足及其產(chǎn)生的原因;分別分析了使用雙螺旋盤管型蓄熱器和翅片型蓄熱器的多聯(lián)機(jī)相變蓄能除霜新系統(tǒng)進(jìn)行蓄能除霜實(shí)驗(yàn)的除霜換向間隔、壓縮機(jī)吸氣壓力/溫度、室內(nèi)機(jī)盤管溫度、恢復(fù)供熱時(shí)間等動(dòng)態(tài)參數(shù),比較兩種換熱器在蓄能除霜中的表現(xiàn),并與常規(guī)除霜參數(shù)進(jìn)行對(duì)比,體現(xiàn)其優(yōu)越性。實(shí)驗(yàn)證明,,多聯(lián)機(jī)空氣源熱泵相變蓄能除霜系統(tǒng)在除霜過程中的除霜時(shí)間、壓縮機(jī)工作環(huán)境、對(duì)室內(nèi)環(huán)境的影響以及節(jié)能方面均有著巨大的提升。 本文的研究工作將為相變蓄能技術(shù)在多聯(lián)機(jī)空氣源熱泵中的應(yīng)用提供理論基礎(chǔ)和技術(shù)儲(chǔ)備。
[Abstract]:Multi - connection is one of the main development directions of the future air source heat pump , but the defrosting problem seriously restricts the further development of the multi - line air source heat pump . In order to solve the problem , a multi - line air source heat pump phase change energy storage defrosting system is designed under the premise of seriously understanding the working principle of the multi - line air source heat pump .

A new method for calculating the defrosting energy consumption of 65 mol % capric acid + 35mol % dodecanoic acid is proposed according to the phase change temperature and latent heat of phase change . A new method for calculating the defrosting energy consumption based on the single defrosting frost water quality of the multi - line air source heat pump is proposed to ensure the accurate saving of the dosage of the phase change material . The fin type phase change heat accumulator is designed , and the heat exchange capacity of the phase change heat accumulator is calculated .

Based on the design experiment flow and the experimental verification requirements , a multi - line phase - change energy storage defrosting experiment table was built , the measuring tool and the data acquisition system were selected . The error analysis was carried out to prove that the measuring accuracy of the experiment table met the use requirement .

On this basis , the normal heating / defrosting , phase change heat storage / defrosting test of the multi - line air source heat pump is completed , and the dynamic data including temperature , pressure , relative humidity , power and other parameters are measured .
Based on the above data , the general heat supply and defrosting characteristics of multi - line are studied , and the shortage of conventional defrosting and the causes are analyzed .
The results show that the defrosting time , the working environment of the compressor , the influence on the indoor environment and the energy saving are greatly improved in the defrosting process of the multi - line air source heat pump phase change energy storage defrosting system .

The research work of this paper will provide theoretical basis and technical reserve for the application of phase change energy storage technology in multi - line air source heat pump .
【學(xué)位授予單位】:哈爾濱工業(yè)大學(xué)
【學(xué)位級(jí)別】:碩士
【學(xué)位授予年份】:2014
【分類號(hào)】:TU83

【參考文獻(xiàn)】

相關(guān)期刊論文 前10條

1 馬曉光;張曉林;李俊升;夏少白;湯鑄先;;相變材料的復(fù)合及其熱性能研究[J];材料科學(xué)與工藝;2008年05期

2 林道光;李小華;唐景立;;空氣源熱泵除霜研究[J];建筑節(jié)能;2013年04期

3 胡文舉;姜益強(qiáng);姚楊;馬最良;;制冷劑為循環(huán)介質(zhì)的螺旋盤管相變蓄熱器數(shù)學(xué)模型[J];哈爾濱工程大學(xué)學(xué)報(bào);2008年10期

4 韓志濤;姚楊;馬最良;姜益強(qiáng);;空氣源熱泵蓄能熱氣除霜新系統(tǒng)與實(shí)驗(yàn)研究[J];哈爾濱工業(yè)大學(xué)學(xué)報(bào);2007年06期

5 于永生;井強(qiáng)山;孫雅倩;;低溫相變儲(chǔ)能材料研究進(jìn)展[J];化工進(jìn)展;2010年05期

6 董建鍇;姜益強(qiáng);姚楊;胡文舉;;空氣源熱泵相變蓄能除霜特性實(shí)驗(yàn)研究[J];湖南大學(xué)學(xué)報(bào)(自然科學(xué)版);2011年01期

7 秦素梅;;熱氣旁通在空氣源熱泵機(jī)組中的應(yīng)用[J];機(jī)電產(chǎn)品開發(fā)與創(chuàng)新;2011年04期

8 黃虎,李志浩,束鵬程;風(fēng)冷熱泵除霜控制方法分析[J];建筑熱能通風(fēng)空調(diào);1999年03期

9 胡凌霄;付海明;劉棟棟;陳軍;;采用肋片強(qiáng)化相變蓄熱器傳熱的模擬分析[J];能源技術(shù);2009年06期

10 李九如;孔祥鵬;王妍;許銘濤;孟令坤;;空氣源熱泵除霜?jiǎng)討B(tài)特性實(shí)驗(yàn)臺(tái)研制[J];哈爾濱理工大學(xué)學(xué)報(bào);2012年05期