發(fā)電機短路試驗中轉(zhuǎn)子接地保護誤動作分析及關(guān)鍵問題探討
發(fā)布時間:2018-06-26 04:00
本文選題:發(fā)電機短路試驗 + 轉(zhuǎn)子接地保護; 參考:《水力發(fā)電》2017年09期
【摘要】:針對自并勵水輪發(fā)電機組在短路試驗中發(fā)生轉(zhuǎn)子一點接地保護誤動作的問題,對勵磁系統(tǒng)和繼電保護原理等方面進行了理論分析,探討了變壓器運行特性及高次諧波的影響。通過現(xiàn)場測試、錄制電壓波形等方法,查找出保護誤動作原因,并提出了相應(yīng)處理措施。在此基礎(chǔ)上對發(fā)電機短路試驗中的關(guān)鍵問題及注意事項進行了探討。
[Abstract]:In order to solve the problem of rotor one-point grounding protection misoperation in short-circuit test of self-shunt turbine generator set, the excitation system and relay protection principle are theoretically analyzed, and the influence of transformer operation characteristics and high-order harmonics is discussed. Through field test, recording voltage waveform and other methods, find out the cause of protection misoperation, and put forward the corresponding treatment measures. On this basis, the key problems and matters needing attention in generator short circuit test are discussed.
【作者單位】: 水電水利規(guī)劃設(shè)計總院;
【分類號】:TM312
【相似文獻】
相關(guān)期刊論文 前4條
1 王煜;季侃;;注入方波電壓式轉(zhuǎn)子接地保護改進方案[J];水電自動化與大壩監(jiān)測;2011年04期
2 陳浩森;丁威;李光耀;;對三峽地下電站30號機轉(zhuǎn)子接地保護連續(xù)多次動作的行為分析[J];四川電力技術(shù);2013年03期
3 梁彥;蒙碧花;;YWX111—11型轉(zhuǎn)子接地保護裝置誤動原理分析[J];小水電;2012年02期
4 王才;;水輪發(fā)電機轉(zhuǎn)子接地保護的完善及異常情況原因分析[J];水電廠自動化;2006年04期
相關(guān)會議論文 前1條
1 陳俊;嚴偉;沈全榮;;大型水電機組定子和轉(zhuǎn)子接地保護方案[A];中國水力發(fā)電工程學(xué)會繼電保護專業(yè)委員會2008年年會暨學(xué)術(shù)研討會學(xué)術(shù)論文集[C];2008年