500kV隔離開關(guān)熱穩(wěn)特性試驗與分析
[Abstract]:Thermal stability is one of the important performances of the disconnector. In order to determine the thermal stability of the equipment under steady and transient load, a large current test device is used in the laboratory to test the different load conditions of 500kV disconnector. The relationship between the temperature change and time of the equipment is explored, and the test results are analyzed in depth. The experimental and analytical results show that the empirical relationship between current and time is satisfied in the case of steady load current and the classical empirical relationship between temperature rise and overload time of equipment under transient load current condition.
【作者單位】: 華東電網(wǎng)有限公司;電力設(shè)備電氣絕緣國家重點實驗室西安交通大學(xué);
【分類號】:TM564.1
【參考文獻(xiàn)】
相關(guān)期刊論文 前2條
1 葉自強(qiáng);朱和平;;提高輸電線路輸送容量的研究[J];電網(wǎng)技術(shù);2006年S1期
2 胡桅林,李志信,朱南強(qiáng);高壓隔離開關(guān)溫升的研究[J];高壓電器;1988年01期
【共引文獻(xiàn)】
相關(guān)期刊論文 前10條
1 黃斌;蘇文宇;劉小波;徐姍姍;徐珍;;電容器連接組件過熱原因分析與設(shè)計改進(jìn)[J];電力電容器與無功補(bǔ)償;2012年03期
2 彭向陽;周華敏;鄭曉光;;架空線路在線監(jiān)測系統(tǒng)建設(shè)及運行分析[J];電力建設(shè);2009年09期
3 竇飛;喬黎偉;;架空線路輸電能力計算[J];電力建設(shè);2010年12期
4 劉小波;黃斌;蘇文宇;;GW4(A)-40.5DW型隔離開關(guān)導(dǎo)電帶過熱原因分析及改良設(shè)計[J];高壓電器;2012年12期
5 吳婧;文俊;溫家良;韓民曉;彭暢;王宇;吳銳;;高壓直流三極輸電特性分析[J];電網(wǎng)技術(shù);2013年01期
6 戴沅;聶聳;程養(yǎng)春;王偉然;;輸電線路動態(tài)增容載流量計算模型綜述[J];廣東電力;2012年11期
7 文俊;溫家良;殷威揚(yáng);別曉玉;吳婧;韓民曉;;高壓直流三極輸電技術(shù)[J];電網(wǎng)技術(shù);2013年08期
8 袁勇;;架空線路監(jiān)測系統(tǒng)電源方案[J];電子世界;2013年14期
9 王孔森;孫旭日;盛戈v,
本文編號:2215237
本文鏈接:http://sikaile.net/kejilunwen/dianlilw/2215237.html