復(fù)雜和應(yīng)涌流及其對電流差動保護的影響
發(fā)布時間:2018-06-11 19:17
本文選題:變壓器 + 和應(yīng)涌流; 參考:《電力系統(tǒng)自動化》2014年06期
【摘要】:目前大多數(shù)和應(yīng)涌流機理分析采用運行變壓器空載模型,對運行變壓器非空載情況下的復(fù)雜和應(yīng)涌流研究較為有限。文中推導(dǎo)了當(dāng)一臺變壓器空投、另一臺變壓器非空載運行時,變壓器磁鏈、電源電流以及運行變壓器負(fù)載電流的解析表達(dá)式,分析了復(fù)雜和應(yīng)涌流的影響因素、關(guān)鍵特征以及對相鄰發(fā)電機電流差動保護的影響。數(shù)字仿真、動模試驗以及現(xiàn)場錄波數(shù)據(jù)驗證了分析結(jié)論的正確性。
[Abstract]:At present, most and should inrush mechanism analysis adopts no-load model of running transformer, and the research on complex and inrush current in non-no-load condition of operating transformer is limited. In this paper, the analytical expressions of flux chain, power supply current and load current of running transformer are derived when one transformer is air-dropped and the other transformer is running without load, and the influence factors of complex and inrush current are analyzed. The key features and the influence on the current differential protection of adjacent generators. Digital simulation, dynamic model test and field recording data verify the correctness of the conclusion.
【作者單位】: 廣東電網(wǎng)公司電力科學(xué)研究院;電力安全與高效湖北省重點實驗室華中科技大學(xué);強電磁工程與新技術(shù)國家重點實驗室華中科技大學(xué);
【基金】:中國南方電網(wǎng)公司科技項目(K-GD2012-324)~~
【分類號】:TM772
【參考文獻(xiàn)】
相關(guān)期刊論文 前10條
1 王陽光;尹項根;游大海;徐天奇;王博;;影響變壓器和應(yīng)涌流的各種因素[J];電工技術(shù)學(xué)報;2009年09期
2 畢大強,王祥珩,李德佳,余高旺,王贊基,王維儉;變壓器和應(yīng)涌流的理論探討[J];電力系統(tǒng)自動化;2005年06期
3 袁宇波,李德佳,陸于平,許揚,李澄;變壓器和應(yīng)涌流的物理機理及其對差動保護的影響[J];電力系統(tǒng)自動化;2005年06期
4 張雪松,何奔騰,張建松;變壓器和應(yīng)涌流的產(chǎn)生機理及其影響因素研究[J];電力系統(tǒng)自動化;2005年06期
5 余高旺,畢大強,王志廣,吳水蘭;變壓器和應(yīng)涌流現(xiàn)象及實例分析[J];電力系統(tǒng)自動化;2005年06期
6 任先文;徐宏雷;趙s,
本文編號:2006366
本文鏈接:http://sikaile.net/kejilunwen/dianlilw/2006366.html
最近更新
教材專著