環(huán)境參數(shù)對(duì)冷卻塔性能影響的綜合分析

發(fā)布時(shí)間:2018-04-25 09:11

  本文選題:冷卻塔 + 性能 ; 參考:《汽輪機(jī)技術(shù)》2017年05期


【摘要】:以某電廠冷卻塔為研究對(duì)象,對(duì)不同環(huán)境參數(shù)下冷卻塔性能進(jìn)行了數(shù)值模擬,研究了環(huán)境溫度和相對(duì)濕度對(duì)冷卻水溫降的綜合影響。結(jié)果表明,隨著相對(duì)濕度的增加,冷卻水溫降減小;環(huán)境溫度越高,相對(duì)濕度對(duì)冷卻水溫降的影響作用越明顯,環(huán)境溫度為5℃時(shí),相對(duì)濕度每增加0.1,冷卻水溫降約減少0.1℃,環(huán)境溫度為35℃時(shí),相對(duì)濕度每增加0.1,冷卻水溫降約減少0.4℃。
[Abstract]:Taking the cooling tower of a power plant as the research object, the performance of the cooling tower under different environmental parameters was numerically simulated, and the comprehensive effects of ambient temperature and relative humidity on the temperature drop of cooling water were studied. The results show that with the increase of relative humidity, the temperature drop of cooling water decreases, and the higher the ambient temperature, the more obvious the effect of relative humidity on the temperature drop of cooling water. When the ambient temperature is 5 鈩,