某小型數(shù)據(jù)中心散熱用泵驅(qū)動回路熱管換熱機組的應(yīng)用研究

發(fā)布時間:2018-05-20 23:01

  本文選題:數(shù)據(jù)中心散熱 + 泵驅(qū)動回路熱管; 參考:《北京工業(yè)大學(xué)學(xué)報》2015年03期


【摘要】:由于泵驅(qū)動回路熱管換熱機組具有低耗能、高能效比(EER)的特點,為了將該機組更好地應(yīng)用于小型數(shù)據(jù)中心,對某小型數(shù)據(jù)中心散熱用泵驅(qū)動回路熱管換熱機組的運行性能進行研究,擬合出其換熱特性曲線,并通過擬合曲線對其進行節(jié)能性分析.分析結(jié)果表明,在過渡季節(jié)及冬季,當(dāng)室外溫度低于15℃時,采用氟泵系統(tǒng)對數(shù)據(jù)中心機房進行散熱能滿足室內(nèi)負荷要求并具有良好的節(jié)能效果,與之前的采用空調(diào)散熱相比節(jié)省電能至少達到36.57%.
[Abstract]:Because the heat pipe heat exchanger of pump drive circuit has the characteristics of low energy consumption and high energy efficiency ratio (EER), in order to better apply this unit to small data center, The operation performance of heat pipe heat exchanger in pump driving circuit of a small data center is studied, and the heat transfer characteristic curve is fitted out, and the energy saving analysis is carried out through the fitting curve. The results show that in the transition season and winter, when the outdoor temperature is lower than 15 鈩,