天堂国产午夜亚洲专区-少妇人妻综合久久蜜臀-国产成人户外露出视频在线-国产91传媒一区二区三区

當(dāng)前位置:主頁 > 科技論文 > 電力論文 >

110kV和220kV變壓器中性點(diǎn)過電壓仿真分析及其保護(hù)探究

發(fā)布時(shí)間:2019-03-04 17:28
【摘要】:目前我國110kV和220kV系統(tǒng)變壓器普遍采用部分中性點(diǎn)接地方式運(yùn)行,變壓器中性點(diǎn)的過電壓保護(hù)采取避雷器和放電間隙并聯(lián)措施,但經(jīng)現(xiàn)場運(yùn)行發(fā)現(xiàn)存在絕緣配合失調(diào)的情況,最常見的故障是系統(tǒng)有效接地時(shí)發(fā)生單相接地故障卻引起間隙誤擊穿,導(dǎo)致停電規(guī)模擴(kuò)大;而棒間隙拒動導(dǎo)致避雷器爆炸和設(shè)備絕緣損壞的事故也多次發(fā)生,亟需進(jìn)一步完善變壓器中性點(diǎn)的接地方式,保證電力系統(tǒng)安全可靠運(yùn)行。本文主要基于兩種思路對此問題進(jìn)行深入探究,第一種是變壓器中性點(diǎn)采用小電抗接地方式,另一種是在目前中性點(diǎn)部分接地方式下,對避雷器和間隙的配合參數(shù)進(jìn)行整定,并對目前間隙的改進(jìn)工作提出建議。變壓器經(jīng)小電抗接地運(yùn)行方式具有防止有效接地系統(tǒng)發(fā)生“失地”現(xiàn)象、限制變壓器中性點(diǎn)短路電流和降低中性點(diǎn)過電壓對系統(tǒng)絕緣損害的優(yōu)勢,且對中性點(diǎn)過電壓的防護(hù),也不再需要裝設(shè)間隙,可有效避免間隙對系統(tǒng)帶來的運(yùn)行隱患。目前國內(nèi)500kV自耦變壓器中性點(diǎn)經(jīng)小電抗接地方式經(jīng)現(xiàn)場運(yùn)行檢驗(yàn),效果良好,而110kV和220kV變壓器中性點(diǎn)采用經(jīng)小電抗接地方式運(yùn)行還處在理論完善和現(xiàn)場試驗(yàn)階段,各文獻(xiàn)對此種方式接地看法不一,有必要對此問題做進(jìn)一步的研究探討,本文主要研究了系統(tǒng)接入小電抗后變壓器及系統(tǒng)零序阻抗變化,并分析了其對中性點(diǎn)短路電流、系統(tǒng)零序阻抗和變壓器中性點(diǎn)絕緣水平的影響;對接地小電抗的裝置進(jìn)行了設(shè)計(jì)和建議小電抗的取值范圍為變壓器零序阻抗的1/3。本文主要還對目前變壓器中性點(diǎn)采用的部分接地方式進(jìn)行優(yōu)化和改進(jìn)。經(jīng)過對多起事故原因的分析研究,發(fā)現(xiàn)中性點(diǎn)處的保護(hù)參數(shù)整定應(yīng)依據(jù)變壓器中性點(diǎn)處實(shí)際過電壓情況來進(jìn)行選擇,但目前用作避雷器和間隙整定參考的卻是標(biāo)準(zhǔn)雷電波和工頻電壓波的放電電壓,導(dǎo)致間隙和避雷器不能可靠保護(hù)中性點(diǎn)絕緣。本文在考慮了變電所現(xiàn)場運(yùn)行的各項(xiàng)影響因素后,對在中性點(diǎn)上引起的雷電過電壓和單相接地工頻過電壓的波形情況利用EMTP仿真軟件進(jìn)行仿真計(jì)算,得到的結(jié)論對間隙和避雷器參數(shù)進(jìn)行整定;然而目前使用的棒間隙仍存在距離調(diào)節(jié)不準(zhǔn)、同心度差和放電分散性高等缺點(diǎn),其在遭受電弧作用時(shí),電極發(fā)生燒蝕,棒間隙距離發(fā)生變化,使得間隙的使用頻率較低,本文對間隙的改進(jìn)也提出了自己的建議。
[Abstract]:At present, partial neutral grounding mode is generally used in China's 110kV and 220kV system transformers. The over-voltage protection of transformer neutral points takes measures of lightning arrester and discharge gap parallel. However, it is found that there is a misalignment of insulation coordination in the field operation. The most common fault is that the single-phase grounding fault occurs when the system is effectively grounded, but it causes the gap breakdown by mistake, which leads to the enlargement of the scale of the power outage. The accidents of lightning arrester explosion and equipment insulation damage caused by bar gap rejection also occur many times. It is urgent to further improve the grounding mode of transformer neutral point to ensure the safe and reliable operation of power system. The first is that the neutral point of transformer is grounded by small reactance, and the other is to adjust the matching parameters of lightning arrester and gap under the current partial grounding mode of neutral point, the first is that the neutral point of transformer is grounded by small reactance, and the other is to adjust the matching parameters of lightning arrester and gap under the current partial neutral grounding mode. At the same time, some suggestions are put forward for the improvement of the gap at present. The operation mode of transformer through small reactance earthing has the advantage of preventing the "ground loss" of effective grounding system, limiting the short circuit current of transformer neutral point and reducing the damage of neutral point overvoltage to the insulation of the system, and the protection of neutral point overvoltage. It is no longer necessary to install clearance, which can effectively avoid the hidden trouble caused by clearance to the system. At present, the neutral point of domestic 500kV auto-transformer has been tested by small reactance grounding mode, and the effect is good. However, the neutral point of 110kV and 220kV transformer is still in the stage of perfect theory and field test, while the neutral point of 110kV and 220kV transformer is running through small reactance grounding mode. It is necessary to do further research on this problem. This paper mainly studies the change of transformer and system zero-sequence impedance after the system is connected with small reactance, and analyzes its short-circuit current to neutral point. The influence of the zero sequence impedance of the system and the insulation level of the transformer neutral point; The small reactance device is designed and suggested that the value range of the small reactance is 1 / 3 of the zero sequence impedance of the transformer. This paper also optimizes and improves the partial grounding method used in transformer neutral point at present. Through the analysis of the causes of many accidents, it is found that the setting of the protection parameters at the neutral point should be based on the actual over-voltage at the neutral point of the transformer. However, the discharge voltage of standard lightning wave and power frequency voltage wave is the reference of lightning arrestor and clearance setting at present, which leads to the unreliable protection of neutral point insulation. After considering the influence factors of substation operation, this paper uses EMTP simulation software to simulate the waveform of lightning overvoltage and single-phase-to-earth power frequency overvoltage caused by neutral point. Finally, the parameters of clearance and arrester are adjusted. However, the gap of rod used at present still has the shortcomings of wrong distance adjustment, poor concentric degree and high dispersion of discharge. Under the action of arc, the electrode is ablative and the distance of rod gap is changed, which makes the use frequency of the gap lower. This paper also puts forward some suggestions for the improvement of gap.
【學(xué)位授予單位】:山西大學(xué)
【學(xué)位級別】:碩士
【學(xué)位授予年份】:2014
【分類號】:TM41

【參考文獻(xiàn)】

相關(guān)期刊論文 前9條

1 蔣偉;吳廣寧;張雪原;王萬崗;王聲學(xué);;單相短路對110kV和220kV變壓器中性點(diǎn)絕緣的影響及其防護(hù)[J];變壓器;2007年11期

2 楊萍;陳鵬;陸彥虎;杜伊;;中性點(diǎn)不接地變壓器的過電壓保護(hù)探討[J];電氣傳動自動化;2010年06期

3 陸國慶;姜新宇;江健武;張勝保;劉順桂;何冰;章彬;;110kV及220kV系統(tǒng)變壓器中性點(diǎn)經(jīng)小電抗接地方式的研究及其應(yīng)用[J];電網(wǎng)技術(shù);2006年01期

4 蔣陸萍;曾祥君;羅志平;;變壓器保護(hù)誤動的分析[J];高電壓技術(shù);2007年09期

5 姚玉斌;吳志良;王丹;李洪;郭峰;;電力系統(tǒng)變壓器模型分析[J];繼電器;2007年24期

6 馬心良;周文俊;韓晉平;喻劍輝;勞斯佳;李小陸;黃燕;;110kV變壓器分級絕緣中性點(diǎn)密封間隙[J];武漢大學(xué)學(xué)報(bào)(工學(xué)版);2012年02期

7 李六零,胡攀峰,邱毓昌;不同變壓器繞組模型對計(jì)算快速暫態(tài)過電壓的影響分析[J];西安交通大學(xué)學(xué)報(bào);2005年10期

8 周建博;李莎;李曉民;;110kV變壓器中性點(diǎn)不接地方式運(yùn)行時(shí)中性點(diǎn)保護(hù)問題研究[J];陜西電力;2012年04期

9 李黎;齊向東;蔡禮;林福昌;郭良福;賴貴友;;石墨電極空氣間隙的自擊穿統(tǒng)計(jì)特性分析[J];中國電機(jī)工程學(xué)報(bào);2012年01期



本文編號:2434472

資料下載
論文發(fā)表

本文鏈接:http://sikaile.net/kejilunwen/dianlilw/2434472.html


Copyright(c)文論論文網(wǎng)All Rights Reserved | 網(wǎng)站地圖 |

版權(quán)申明:資料由用戶b6272***提供,本站僅收錄摘要或目錄,作者需要刪除請E-mail郵箱bigeng88@qq.com
精品综合欧美一区二区三区| 国产精品成人一区二区三区夜夜夜| 九九热九九热九九热九九热| 欧美熟妇一区二区在线| 亚洲日本久久国产精品久久| 日本在线视频播放91| 香蕉尹人视频在线精品| 成人精品一区二区三区在线| 东京热男人的天堂一二三区| 成人免费在线视频大香蕉| 国产日产欧美精品视频| 成人精品一区二区三区综合| 九九热这里只有精品哦| 久久热麻豆国产精品视频| 好吊色欧美一区二区三区顽频 | 99视频精品免费视频| 亚洲乱妇熟女爽的高潮片| 国产精品一区日韩欧美| 国产欧美日产久久婷婷| 白白操白白在线免费观看| 福利一区二区视频在线| 日韩在线视频精品中文字幕| 免费国产成人性生活生活片| 精品午夜福利无人区乱码| 国产精品久久精品国产| 91亚洲精品综合久久| 中文字幕日韩无套内射| 日本人妻精品有码字幕| 国内精品一区二区欧美| 久久这里只有精品中文字幕| 神马午夜福利一区二区| 在线免费视频你懂的观看| 一区二区日本一区二区欧美| 在线一区二区免费的视频| 亚洲熟女国产熟女二区三区| 亚洲国产精品av在线观看| 日本人妻的诱惑在线观看| 国产亚洲精品久久99| 日本高清不卡一二三区| 日韩在线精品视频观看| 亚洲天堂精品在线视频|