110kV和220kV變壓器中性點(diǎn)過電壓仿真分析及其保護(hù)探究
[Abstract]:At present, partial neutral grounding mode is generally used in China's 110kV and 220kV system transformers. The over-voltage protection of transformer neutral points takes measures of lightning arrester and discharge gap parallel. However, it is found that there is a misalignment of insulation coordination in the field operation. The most common fault is that the single-phase grounding fault occurs when the system is effectively grounded, but it causes the gap breakdown by mistake, which leads to the enlargement of the scale of the power outage. The accidents of lightning arrester explosion and equipment insulation damage caused by bar gap rejection also occur many times. It is urgent to further improve the grounding mode of transformer neutral point to ensure the safe and reliable operation of power system. The first is that the neutral point of transformer is grounded by small reactance, and the other is to adjust the matching parameters of lightning arrester and gap under the current partial grounding mode of neutral point, the first is that the neutral point of transformer is grounded by small reactance, and the other is to adjust the matching parameters of lightning arrester and gap under the current partial neutral grounding mode. At the same time, some suggestions are put forward for the improvement of the gap at present. The operation mode of transformer through small reactance earthing has the advantage of preventing the "ground loss" of effective grounding system, limiting the short circuit current of transformer neutral point and reducing the damage of neutral point overvoltage to the insulation of the system, and the protection of neutral point overvoltage. It is no longer necessary to install clearance, which can effectively avoid the hidden trouble caused by clearance to the system. At present, the neutral point of domestic 500kV auto-transformer has been tested by small reactance grounding mode, and the effect is good. However, the neutral point of 110kV and 220kV transformer is still in the stage of perfect theory and field test, while the neutral point of 110kV and 220kV transformer is running through small reactance grounding mode. It is necessary to do further research on this problem. This paper mainly studies the change of transformer and system zero-sequence impedance after the system is connected with small reactance, and analyzes its short-circuit current to neutral point. The influence of the zero sequence impedance of the system and the insulation level of the transformer neutral point; The small reactance device is designed and suggested that the value range of the small reactance is 1 / 3 of the zero sequence impedance of the transformer. This paper also optimizes and improves the partial grounding method used in transformer neutral point at present. Through the analysis of the causes of many accidents, it is found that the setting of the protection parameters at the neutral point should be based on the actual over-voltage at the neutral point of the transformer. However, the discharge voltage of standard lightning wave and power frequency voltage wave is the reference of lightning arrestor and clearance setting at present, which leads to the unreliable protection of neutral point insulation. After considering the influence factors of substation operation, this paper uses EMTP simulation software to simulate the waveform of lightning overvoltage and single-phase-to-earth power frequency overvoltage caused by neutral point. Finally, the parameters of clearance and arrester are adjusted. However, the gap of rod used at present still has the shortcomings of wrong distance adjustment, poor concentric degree and high dispersion of discharge. Under the action of arc, the electrode is ablative and the distance of rod gap is changed, which makes the use frequency of the gap lower. This paper also puts forward some suggestions for the improvement of gap.
【學(xué)位授予單位】:山西大學(xué)
【學(xué)位級別】:碩士
【學(xué)位授予年份】:2014
【分類號】:TM41
【參考文獻(xiàn)】
相關(guān)期刊論文 前9條
1 蔣偉;吳廣寧;張雪原;王萬崗;王聲學(xué);;單相短路對110kV和220kV變壓器中性點(diǎn)絕緣的影響及其防護(hù)[J];變壓器;2007年11期
2 楊萍;陳鵬;陸彥虎;杜伊;;中性點(diǎn)不接地變壓器的過電壓保護(hù)探討[J];電氣傳動自動化;2010年06期
3 陸國慶;姜新宇;江健武;張勝保;劉順桂;何冰;章彬;;110kV及220kV系統(tǒng)變壓器中性點(diǎn)經(jīng)小電抗接地方式的研究及其應(yīng)用[J];電網(wǎng)技術(shù);2006年01期
4 蔣陸萍;曾祥君;羅志平;;變壓器保護(hù)誤動的分析[J];高電壓技術(shù);2007年09期
5 姚玉斌;吳志良;王丹;李洪;郭峰;;電力系統(tǒng)變壓器模型分析[J];繼電器;2007年24期
6 馬心良;周文俊;韓晉平;喻劍輝;勞斯佳;李小陸;黃燕;;110kV變壓器分級絕緣中性點(diǎn)密封間隙[J];武漢大學(xué)學(xué)報(bào)(工學(xué)版);2012年02期
7 李六零,胡攀峰,邱毓昌;不同變壓器繞組模型對計(jì)算快速暫態(tài)過電壓的影響分析[J];西安交通大學(xué)學(xué)報(bào);2005年10期
8 周建博;李莎;李曉民;;110kV變壓器中性點(diǎn)不接地方式運(yùn)行時(shí)中性點(diǎn)保護(hù)問題研究[J];陜西電力;2012年04期
9 李黎;齊向東;蔡禮;林福昌;郭良福;賴貴友;;石墨電極空氣間隙的自擊穿統(tǒng)計(jì)特性分析[J];中國電機(jī)工程學(xué)報(bào);2012年01期
,本文編號:2434472
本文鏈接:http://sikaile.net/kejilunwen/dianlilw/2434472.html