泰州地區(qū)110kV輸電線路防雷技術(shù)研究
[Abstract]:The rapid growth of our country's economy is accompanied by the rapid expansion of the electric demand, and the scale of the power system is gradually expanding, and the higher requirements are put forward for the safe operation and reliable power supply of the power grid. In Taizhou, the user's electricity demand and economy need to continuously increase the installed capacity in the area, and construct the grid structure. Taizhou power network is an important hub of Jiangsu, which influences the safety and stability of the Jiangsu power grid and even the East China power grid. The rising trend of the trip accident of the power transmission line caused by the lightning strike in Taizhou area has seriously affected the normal operation of the power system, and the analysis and corresponding improvement measures are urgently needed. In order to solve the problem that the lightning protection measures of the power transmission line in Taizhou area are not sufficient, the paper studies the lightning protection scheme on the premise of detailed understanding of the comprehensive lightning protection measures. In this paper, the current situation of lightning strike in Taizhou area is analyzed and the situation of the power grid in the region is analyzed. The lightning environment and the lightning trip condition in Taizhou area are analyzed and the general rule of the cause of lightning trip in this area is summarized. Then, the lightning protection measures in Taizhou area are tested and analyzed, and the application effect of these measures is verified, including the reduction of the grounding resistance, the increase of the lightning protection equipment and other lightning protection technologies. The risk grade of the lightning trip of the power transmission line is divided, and a lightning trip risk assessment is carried out based on the 110kV raw horse line in the Taizhou area, and the specific lightning protection modification measures are put forward according to the evaluation result, which comprises the following steps of: improving the insulation level of the line pole tower and reducing the grounding resistance of the tower, The protection angle of the line is reduced, the line lightning arrester is used and the unbalanced insulation is adopted to reduce the occurrence of the lightning damage accident of the line. The data from the front and back of the lightning protection control shows that the lightning protection technology based on the line risk level has a remarkable application effect.
【學(xué)位授予單位】:華北電力大學(xué)(北京)
【學(xué)位級別】:碩士
【學(xué)位授予年份】:2017
【分類號】:TM863
【參考文獻(xiàn)】
相關(guān)期刊論文 前10條
1 歐陽仁樂;;1000kV桿塔防雷研究[J];電氣技術(shù);2014年11期
2 張榆;劉念;秦斌;徐誠;;1000kV變電站雷電侵入波防護(hù)分析[J];四川電力技術(shù);2013年03期
3 姚陳果;王婷婷;楊慶;司馬文霞;;特高壓交流輸電線路繞擊耐雷性能仿真分析[J];高電壓技術(shù);2013年03期
4 李侶;鄒建章;;帶間隙避雷器在輸電線路防雷中若干問題的探討[J];江西電力;2013年01期
5 馮亮;梁沛然;;基于ATP-EMTP的輸電線路防雷仿真[J];煤礦機(jī)電;2013年01期
6 梁方建;管珊蓮;張回力;周鑫;師曉林;;單避雷線在輸電線路防雷中的應(yīng)用探討[J];電瓷避雷器;2012年03期
7 彭向陽;李振;李志峰;王希;余占清;何金良;;桿塔接地電阻對同塔多回線路防雷性能的影響[J];高電壓技術(shù);2011年12期
8 陳冬;劉建華;賈晨曦;;基于ATP-EMTP的耐雷水平研究[J];電瓷避雷器;2011年05期
9 敬海兵;張彼德;;1000kV特高壓交流輸電線路防雷電繞擊技術(shù)[J];廣東電力;2011年09期
10 蔣平;楊琳;;降低桿塔沖擊接地阻抗方法[J];四川電力技術(shù);2011年03期
相關(guān)碩士學(xué)位論文 前3條
1 王葉偉;江西省輸電線路差異化防雷技術(shù)應(yīng)用及評估[D];華北電力大學(xué);2013年
2 張戰(zhàn)彬;邢臺西部電網(wǎng)輸電線路防雷改進(jìn)措施研究[D];華北電力大學(xué)(河北);2009年
3 許志元;山區(qū)高壓輸電線路雷擊規(guī)律及對策研究[D];廣西大學(xué);2008年