高位收水冷卻塔結(jié)構(gòu)優(yōu)化模擬分析
發(fā)布時(shí)間:2018-02-17 06:50
本文關(guān)鍵詞: 高位收水冷卻塔 數(shù)值模擬 擋水板 收水裝置 出處:《汽輪機(jī)技術(shù)》2017年05期 論文類(lèi)型:期刊論文
【摘要】:通過(guò)建立高位收水冷卻塔內(nèi)收水單元的三維數(shù)值模型,利用Fluent對(duì)其進(jìn)行了數(shù)值模擬,分析了不同擋水板位置對(duì)單元內(nèi)流場(chǎng)、水滴飄零損失以及高位收水冷卻塔通風(fēng)量的影響,模擬結(jié)果表明:當(dāng)擋水板的角度為45°板長(zhǎng)為0.2m時(shí),塔通風(fēng)量最大,0m/s條件下的塔通風(fēng)量達(dá)到11 920kg/s,較不加擋水板時(shí)提高8.69%,證明此時(shí)的收水裝置阻力最低,效果最佳。
[Abstract]:Through the establishment of a three-dimensional numerical model of the intake unit in a high water intake cooling tower, the numerical simulation of the unit is carried out by using Fluent. The effects of different water baffle positions on the flow field, droplet drift loss and ventilation of the high water intake cooling tower are analyzed. The simulation results show that when the angle of the baffle is 45 擄and the length of the plate is 0.2m, the ventilation capacity of the tower reaches 11 920 kg / s when the maximum ventilation capacity is 0 m / s, which is 8.69 kg / s higher than that without the baffle. It is proved that the water collecting device has the lowest resistance and the best effect.