【摘要】:筆者對大連某原生污水源熱泵供熱供冷系統(tǒng)進行了實測,獲得了該系統(tǒng)供暖季和供冷季的運行數(shù)據(jù),供暖季污水溫度平均值為10.45℃,機組和系統(tǒng)平均COP分別為5.02和3.93;供冷季污水溫度平均值為18.43℃,供冷季機組和系統(tǒng)平均COP分別為6.26和4.54。為了進一步減少污水源熱泵系統(tǒng)的運行能耗,提高系統(tǒng)COP,一方面對污水換熱器換熱系數(shù)進行測試研究,與運行初期相比污水換熱器換熱系數(shù)下降了50.08%,更換換熱器后,機組和系統(tǒng)COP分別提高了16.08%和11.36%,說明污水源熱泵系統(tǒng)定期清潔和更換換熱器的重要性;另一方面對污水源熱泵機組變工況運行時蒸發(fā)器側(cè)和冷凝器側(cè)進水溫度和流量對機組性能影響進行分析,基于Data Fit軟件建立了機組性能隨蒸發(fā)器和冷凝器進水溫度和流量變化的數(shù)學(xué)模型,并基于TRNSYS平臺對系統(tǒng)負荷側(cè)水泵定頻和變頻工況分別進行模擬,變頻運行機組和系統(tǒng)COP均增加,系統(tǒng)累計能耗減少約18.52%。
[Abstract]:The author measured the heating and cooling system of a raw sewage source heat pump in Dalian, and obtained the operation data of the system in heating season and cooling season. The average temperature of sewage in heating season was 10.45 鈩,
本文編號:2253943
[Abstract]:The author measured the heating and cooling system of a raw sewage source heat pump in Dalian, and obtained the operation data of the system in heating season and cooling season. The average temperature of sewage in heating season was 10.45 鈩,
本文編號:2253943
本文鏈接:http://sikaile.net/jianzhugongchenglunwen/2253943.html