基于自然冷源應(yīng)用的數(shù)據(jù)中心節(jié)能潛力研究
發(fā)布時間:2018-07-27 18:11
【摘要】:數(shù)據(jù)中心高能耗問題大大阻礙了信息產(chǎn)業(yè)的發(fā)展,自然冷源利用是實(shí)現(xiàn)數(shù)據(jù)中心節(jié)能降耗的關(guān)鍵技術(shù)手段。文章以數(shù)據(jù)中心自然冷源利用為研究對象,確定了蒸發(fā)冷卻間接供冷方式下自然冷源利用臨界濕球溫度的推薦值;分析了全國主要?dú)夂騾^(qū)自然冷源利用潛力;提出了自然冷源利用敏感性的概念;以夏熱冬暖地區(qū)某典型數(shù)據(jù)中心為例進(jìn)行了自然冷源利用的節(jié)能效果分析。結(jié)果表明:數(shù)據(jù)中心自然冷源利用的臨界濕球溫度上限為16℃時,全國大部分地區(qū)的自然冷源可利用率超過50%;溫和地區(qū)自然冷源敏感性最高;夏熱冬暖地區(qū)數(shù)據(jù)中心利用自然冷源時,全年綜合COP值可提高23.7%,節(jié)能率為19.2%。
[Abstract]:The problem of high energy consumption in the data center has greatly hindered the development of the information industry. The utilization of natural cold sources is the key technical means to realize the energy saving and consumption reduction of the data center. The article uses the natural cold source of the data center as the research object, and determines the recommended value of the critical wet bulb temperature for the natural cold source and profit under the indirect cooling mode of the evaporative cooling. The natural cold source utilization potential in the main climate area was used, and the concept of natural cold source utilization sensitivity was put forward. A typical data center in hot summer warm winter warm area was taken as an example to analyze the energy saving effect of natural cold source. The result showed that the natural cold of the natural cold source in the data center was 16 degrees centigrade when the limit of the critical wet bulb temperature was used, and the natural cold in most areas of the country was cold. The source utilization rate is over 50%, and the natural cold source in the mild area is the most sensitive. The comprehensive COP value can be increased by 23.7% and the energy saving rate is 19.2%. in the summer heat and winter warm area data center using natural cold source.
【作者單位】: 中國科學(xué)院廣州能源研究所;東北電力大學(xué);
【基金】:廣東省科技計(jì)劃項(xiàng)目(2015B090901012;2013A011404001) 廣東省新能源和可再生能源研究開發(fā)與應(yīng)用重點(diǎn)實(shí)驗(yàn)室基金項(xiàng)目(Y709jl1001)
【分類號】:TK018;TP308
本文編號:2148721
[Abstract]:The problem of high energy consumption in the data center has greatly hindered the development of the information industry. The utilization of natural cold sources is the key technical means to realize the energy saving and consumption reduction of the data center. The article uses the natural cold source of the data center as the research object, and determines the recommended value of the critical wet bulb temperature for the natural cold source and profit under the indirect cooling mode of the evaporative cooling. The natural cold source utilization potential in the main climate area was used, and the concept of natural cold source utilization sensitivity was put forward. A typical data center in hot summer warm winter warm area was taken as an example to analyze the energy saving effect of natural cold source. The result showed that the natural cold of the natural cold source in the data center was 16 degrees centigrade when the limit of the critical wet bulb temperature was used, and the natural cold in most areas of the country was cold. The source utilization rate is over 50%, and the natural cold source in the mild area is the most sensitive. The comprehensive COP value can be increased by 23.7% and the energy saving rate is 19.2%. in the summer heat and winter warm area data center using natural cold source.
【作者單位】: 中國科學(xué)院廣州能源研究所;東北電力大學(xué);
【基金】:廣東省科技計(jì)劃項(xiàng)目(2015B090901012;2013A011404001) 廣東省新能源和可再生能源研究開發(fā)與應(yīng)用重點(diǎn)實(shí)驗(yàn)室基金項(xiàng)目(Y709jl1001)
【分類號】:TK018;TP308
【相似文獻(xiàn)】
相關(guān)期刊論文 前4條
1 許家琪;梁永建;代勇;許偉明;;燃?xì)饫錈犭娙?lián)供系統(tǒng)在數(shù)據(jù)中心的應(yīng)用[J];發(fā)電與空調(diào);2012年05期
2 舒文瓊;;張?jiān)朴?數(shù)據(jù)中心亟待向能源基地遷徙[J];通信世界;2010年37期
3 肖蔚然;孫錦余;陳鋼;蘭靜;;天然氣分布式能源在數(shù)據(jù)中心能源供應(yīng)的應(yīng)用研究[J];節(jié)能;2014年02期
4 何仲陽;錢曉棟;周紅;李震;張興;;服務(wù)器功率溫升矩陣分配法[J];工程熱物理學(xué)報;2013年03期
相關(guān)碩士學(xué)位論文 前1條
1 王臻;基于動態(tài)調(diào)頻的數(shù)據(jù)中心節(jié)能調(diào)度策略研究[D];南京大學(xué);2016年
,本文編號:2148721
本文鏈接:http://sikaile.net/kejilunwen/jisuanjikexuelunwen/2148721.html
最近更新
教材專著