環(huán)境側風下間接空冷塔水溫分布特性的研究
[Abstract]:The distribution of water temperature in natural ventilation indirect air cooling tower is of great significance for the optimization of winter antifreeze measures. For an indirect air-cooling system of a 660MW unit, a three-dimensional numerical model for calculating the flow heat transfer on the side of an air-cooled tower is established in this paper. The correctness of the model is verified by combining the design conditions of the system, and the environmental temperature is calculated and analyzed from the system point of view. The influence of ambient wind speed on the distribution of water temperature at the outlet of cooling column, cooling triangle, cooling fan section and air cooling tower. It is pointed out that the environmental temperature has little effect on the water temperature imbalance difference at the outlet of the air cooling tower, and the distribution of the water temperature at the outlet of the air cooling tower is representative under a certain ambient temperature, and the cooling performance of the air cooled tower is deteriorated by the environmental wind. In order to prevent the cooling tube bundle from freezing, the control value of air cooling tower outlet water temperature should be increased with the increase of environmental wind speed in order to prevent the cooling tube bundle from freezing in order to increase the unbalanced temperature difference at the outlet water temperature, but the minimum value of the water temperature at the outlet of the cooling tube bundle has little effect on the minimum value of the water temperature at the outlet of the cooling tube bundle.
【作者單位】: 山東大學能源與動力工程學院;
【基金】:國家自然科學基金項目(51606112)~~
【分類號】:TM621
【相似文獻】
相關期刊論文 前10條
1 卜永東,陳曉忠,石維柱,史建良,彭福瑞;空冷塔流場的分析研究[J];內蒙古電力技術;2000年06期
2 白永軍,孔昭文,馬進超,孫耀東,李佐;空冷塔外置尖峰冷卻器的試驗[J];內蒙古電力技術;2003年06期
3 張曉東,鄭永剛,王清照;空冷塔內外流場的數(shù)值分析[J];熱能動力工程;2000年01期
4 崔虹;孫成江;;國內最大空冷塔的帶肋筒壁施工[J];武漢大學學報(工學版);2007年S1期
5 陳曉忠,卜永東,樊澤國;豐鎮(zhèn)電廠~#3機空冷塔百葉窗振動問題的分析與處理措施探討[J];內蒙古電力技術;1994年04期
6 曲新江;空冷塔在外風作用下支柱應力狀態(tài)的試驗分析[J];內蒙古電力技術;2001年03期
7 王殿武;空冷塔散熱器泄漏分析及防漏措施探討[J];電力學報;1999年04期
8 鄭克義,,郭振國,牛寶新;空冷塔增裝預熱/冷卻裝置的可行性研究[J];華北電力技術;1994年10期
9 崔傳濤;王運民;;火力發(fā)電廠空冷塔初始溫差的優(yōu)化設計[J];汽輪機技術;2008年01期
10 李文海;空冷塔散熱器表面噴淋裝置的應用[J];華北電力技術;1997年10期
相關博士學位論文 前2條
1 席新銘;大型間接空冷塔空氣流動特性及流場優(yōu)化研究[D];華北電力大學;2015年
2 張薇;電站間接空冷散熱器和空冷塔流動傳熱特性研究[D];華北電力大學(北京);2016年
相關碩士學位論文 前6條
1 周二奇;660MW機組四塔合一式空冷塔傳熱性能的數(shù)值模擬[D];華北電力大學;2016年
2 向同瓊;間接空冷機組空冷塔翅墻結構優(yōu)化及數(shù)值模擬研究[D];華北電力大學;2014年
3 賀亞楠;大型間接空冷塔優(yōu)化設計研究[D];華北電力大學;2014年
4 李峰;海勒式間接空冷塔性能研究與改造[D];華北電力大學(北京);2006年
5 柴艷琴;SCAL型間接空冷塔內外流場流動特性的數(shù)值模擬及分析[D];華北電力大學;2014年
6 朱正茂;發(fā)電廠冷卻系統(tǒng)運行特性研究[D];華北電力大學;2000年