基于可移動特高頻天線陣列的變電站站域放電源檢測與定位研究
發(fā)布時間:2018-01-15 03:23
本文關(guān)鍵詞:基于可移動特高頻天線陣列的變電站站域放電源檢測與定位研究 出處:《中國電機工程學報》2017年10期 論文類型:期刊論文
更多相關(guān)文章: 變電站 局部放電 特高頻 天線陣列 檢測 定位 天線陣列優(yōu)化布置 時差估計 檢測與定位系統(tǒng)
【摘要】:基于特高頻天線陣列的局部放電檢測方法已被應(yīng)用于敞開式變電站(air-insulated substations,AIS)站域的局部放電巡檢,但目前裝置存在定位精度低等缺點。該文針對變電站局部放電去噪方法、傳感器陣列優(yōu)化布置、定位算法及檢測系統(tǒng)開發(fā)等方面開展了深入研究。針對電暈噪聲、手機通訊信號及非脈沖噪聲,提出了合理選取檢測頻帶、硬件陷波器及能量陡度閾值等去噪方法;通過克拉美羅下界分析及定位均方根誤差仿真對天線陣列布置進行了優(yōu)化,選取為4×1m的菱形天線陣;采用基于最大似然估計的概率定位法求解時差定位方程組,綜合多次局部放電信號定位結(jié)果,可降低時差估計誤差的影響,提高了定位準確度。開發(fā)了變電站局部放電檢測與定位系統(tǒng),包括超寬帶全向雙錐天線、信號調(diào)理電路及信號高速采集分析單元,用于110kV AIS站域局部放電檢測,測試結(jié)果驗證了系統(tǒng)的有效性及定位準確性。
[Abstract]:UHF partial discharge detection method based on antenna array has been applied to open type substation (air-insulated substations AIS) partial discharge inspection station domain, but the device has low positioning accuracy. In this paper, partial discharge denoising method for substation, sensor array optimization, to carry out in-depth study of the localization algorithm and detection system the development of other aspects. For corona noise, mobile phone signal and non impulse noise, put forward the reasonable selection of hardware detection band, notch filter and energy gradient threshold denoising method; the Cramer Rao lower bound analysis and positioning of the root mean square error of antenna array simulation layout has been optimized, selected for the diamond antenna array of 4 * 1m the group; probabilistic localization method for solving the time difference location equation based on maximum likelihood estimation, integrated multiple PD location results, can reduce the estimation error when the difference The effect, to improve the positioning accuracy. The development of the detection and location of partial discharge system of substation, including ultra wideband omnidirectional antenna, signal conditioning circuit and signal acquisition and analysis unit for 110kV station AIS domain partial discharge detection, the test results verify the validity and accuracy of the positioning system.
【作者單位】: 電力設(shè)備電氣絕緣國家重點實驗室(西安交通大學);
【基金】:國家自然科學基金項目(51521065) 國家電網(wǎng)公司科技項目(5226SX15001R)~~
【分類號】:TM63;TM855
【正文快照】: 0引言 局部放電(以下簡稱局放)檢測是電力設(shè)備絕緣狀態(tài)評估的重要手段[1-3]。特高頻法(ultra-highfrequency,UHF)具有抗干擾性能佳及可實現(xiàn)放電源定位等優(yōu)點,近年來得到了國內(nèi)外的普遍認可[4-6]。目前國內(nèi)外開展的UHF局放檢測,通常都是將傳 感器固定安裝在氣體絕緣組合電器
【相似文獻】
相關(guān)期刊論文 前3條
1 呂曉輝;;CART矢量天線空間電磁場分析[J];科技信息(學術(shù)研究);2007年15期
2 ;文獻報導[J];電波與天線;1994年04期
3 ;[J];;年期
,本文編號:1426585
本文鏈接:http://sikaile.net/kejilunwen/dianlidianqilunwen/1426585.html
最近更新
教材專著