【摘要】:為研究自動(dòng)噴水滅火技術(shù)對高大空間建筑火災(zāi)控火性能的影響,按照高大空間公共建筑和廠房的實(shí)際火災(zāi)場景,開展自動(dòng)噴水滅火技術(shù)全尺寸火災(zāi)試驗(yàn)和數(shù)值模擬計(jì)算。選定的噴頭流量系數(shù)為K-161,安裝高度為18 m,噴水強(qiáng)度分別為20和25 L/(min·m2)。試驗(yàn)結(jié)果顯示,在該火災(zāi)場景中,第1只噴頭在點(diǎn)火后3~4 min動(dòng)作,噴頭開放數(shù)為3~4只即能成功控制火勢的增長和蔓延,頂板下的最高溫度為120℃,距火災(zāi)試驗(yàn)?zāi)P?.4 m處的最高溫度為20℃。數(shù)值模擬計(jì)算與實(shí)體火試驗(yàn)結(jié)論基本一致,說明高大空間建筑采用自動(dòng)噴水滅火系統(tǒng),能達(dá)到很好的控火甚至是滅火效果。
[Abstract]:In order to study the influence of automatic sprinkler technology on fire control performance of tall space buildings, the full-scale fire test and numerical simulation calculation of automatic sprinkler technology are carried out according to the actual fire scene of large space public buildings and factory buildings. The flow coefficient of the selected sprinkler is K 鈮,
本文編號:2512824
[Abstract]:In order to study the influence of automatic sprinkler technology on fire control performance of tall space buildings, the full-scale fire test and numerical simulation calculation of automatic sprinkler technology are carried out according to the actual fire scene of large space public buildings and factory buildings. The flow coefficient of the selected sprinkler is K 鈮,